Table 300.5 Minimum Cover Requirements, Nominal Burial in Millimeter (Inches) 
Type of Wiring Method or Circuit
  Column 1 Column 2 Column 3 Column 4 Column 5
Direct Burial Cables or Conductors Rigid Metal Conduit or Intermediate Metal Conduit  Nonmetallic Raceways Listed for Direct Burial Without Concrete Encasement or Other Approved Raceways Residential Branch Circuits Rated 120 Volts or Less with GFCI Protedtion and Maximum Overcurrent Protection of 20 Amperes Circuits for Control of Irrigation and Landscape Lighting Limited to Not More Than 30 Volts and Installed with Type UF or in Other Identified Cable or Raceway
Location of Wiring Method or mm  in. mm  in. mm  in. mm  in. mm  in.
Circuit
All locations not specified below 600 24 150 6 450 18 300 12 150 6
       
In trench below 50-mm (2-in.) thick concrete or equivalent 450 18 150 6 300 12 150 6 150 6
         
Under a building 0 0 0 0 0 0 0 0 0 0
(in raceway only)     (in raceway only) (in raceway only)
Under minimum of 102-mm (4-in.)  450 18 100 4 100 4 150 6 150 6
thick concrete exterior slab with no        (direct burial)  
vehicular traffic and the slab             
extending not less than 152 mm (6 in.)        100 4  
beyond the underground installation       (in raceway)  
             
Under streets, highways, roads, 600 24 600 24 600 24 600 24 600 24
alleys, driveways, and parking        
lots        
One- and two-family dwelling 450 18 450 18 450 18 300 12 450 18
driveways and outdoor        
parking areas, and used only        
for dwelling-related purposes        
In or under airport runways, 450 18 450 18 450 18 450 18 450 18
including adjacent areas        
where trespassing prohibited        
Notes:                    
1.   Cover is defined as the shortest distance in millimeters (inches) measured between a point on the top surface of
any direct-buried conductor, cable, conduit, or other raceway and the top surface of finished grade, concrete, or similar cover.
2.   Raceways approved for burial only where concrete encased shall require concrete envelope not less than 50 mm
(2 in.) thick.
3.   Lesser depths shall be permitted where cables and conductors rise for terminations or splices or where access is otherwise required.
4.   Where one of the wiring method types listed in Columns 1–3 is used for one of the circuit types in Columns 4 and 5, the shallowest depth of burial shall be permitted.
5.   Where solid rock prevents compliance with the cover depths specified in this table, the wiring shall be installed in metal or nonmetallic raceway permitted for direct burial. The raceways shall be covered by a minimum of 50 mm
(2 in.) of concrete extending down to rock.