Article 430.72(B) |
|
1) |
Separate Overcurrent Protection. Where the motor
branch-circuit short-circuit and ground-fault protective device
does not provide protection in accordance with 430.72(B)(2),
separate overcurrent protection shall be provided. The
over-current protection shall not exceed the values specified in
Column A of Table 430.72(B).
|
|
2) |
Branch-Circuit Overcurrent Protective Device. Conductors shall
be permitted to be protected by the motor branch-circuit
short-circuit and ground-fault protective de-vice and shall
require only short-circuit and ground-fault protection. Where the
conductors do not extend beyond the motor control equipment
enclosure, the rating of the protective device(s) shall not exceed
the value specified in Column B of Table 430.72(B). Where the
conductors ex-tend beyond the motor control equipment enclosure,
the rating of the protective device(s) shall not exceed the value
specified in Column C of Table 430.72(B). |
|
|
Table 430.72(B) Maximum Rating of Overcurrent Protective Device in
Amperes |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Protection Provided by Motor Branch-Circuit Protective Device(s) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Column A |
|
Column B |
|
Column C |
|
|
|
Separate Protection |
|
Conductors Within |
|
Conductors Extend Beyond |
|
|
|
Provided |
|
Enclosure |
|
Enclosure |
|
Control |
|
|
|
|
|
|
|
|
|
|
Circuit |
|
Aluminum or |
|
Aluminum or |
|
Aluminum or |
|
Conductor |
|
Copper-Clad |
|
Copper-Clad |
|
Copper-Clad |
|
Size (AWG) |
|
Copper |
Aluminum |
|
Copper |
Aluminum |
|
Copper |
Aluminum |
|
18 |
|
7 |
- |
|
25 |
- |
|
7 |
- |
|
16 |
|
10 |
- |
|
40 |
- |
|
10 |
- |
|
14 |
|
(Note 1) |
- |
|
100 |
- |
|
45 |
- |
|
12 |
|
(Note 1) |
(Note 1) |
|
120 |
100 |
|
60 |
45 |
|
10 |
|
(Note 1) |
(Note 1) |
|
160 |
140 |
|
90 |
75 |
|
Larger than 10 |
|
(Note 1) |
(Note 1) |
|
(Note 2) |
(Note 2) |
|
(Note 3) |
(Note 3) |
| |
|
|
|
|
|
|
|
|
|
|
Notes: |
|
|
|
|
|
|
|
|
|
|
1. Value specified in 310.15 as applicable. |
|
|
|
|
|
|
|
2. 400 percent of value specified in Table 310.17 for 60°C conductors. |
|
|
|
|
3. 300 percent of value specified in Table 310.16 for 60°C conductors. |
|
|
|
| |
|
|
|
|
|
|
|
|
|