Click Here
For Troubleshooting aid.
 
  Notice:   
  NEC is a registered trademark of the National Fire Protection Association, Inc.  All NEC references by Electrical Helper are interpretations of the NEC by the Electrical Helper staff and are not NEC statements. The official position of the NEC requires that the NEC be referred to in its entirety.   
     
     
  Article 430.22  
  Describing a single motor states: Conductors supplying a single motor for continuous duty shall have an ampacity of not less that 125 percent of the motor's full-load current determined by 430.6(A)(1).  
     
     
  Article 430-24  
    Several Motors or a combination motor and other loads states: Conductors supplying several motors, or a motor(s) and other load(s) shall have an ampacity of not less than 125 percent of the full-load current rating of the highest rated motor plus the sum of the full-load current ratings of all the other motors in the group, as determined by 430.6(A), plus the ampacity required for the other loads.  
     
  Please Note:  
    Section 430 of the NEC is extensive and should be referred to in detail before sizing your conductors.  
     
  Click Here For 3-Phase AC Motor Full Load Current Ratings.  