460 Volt 3 Phase 1800 RPM 30HP
Thermal Magnetic Breaker Size
80 Amp
Dual Element Time Delay Fuse Size
60 Amp
Manual Motor Starter Protector
34-50 A
IEC Contactor Size
(Snap together with an RMSP motor starter protector to make a complete electro-mechanical combination starter)
50 Amp
NEMA Rated Starter Size
2
Power Factor Capacitor
8.3KVAR