480 Volt 3 Phase 1800 RPM  25HP
Thermal Magnetic Breaker Size 70 Amp
Dual Element Time Delay Fuse Size 40 Amp
Manual Motor Starter Protector 28-40 A
IEC Contactor Size
(Snap together with an RMSP motor starter protector to make a complete electro-mechanical combination starter)
40 Amp
NEMA Rated Starter Size 2
Power Factor Capacitor 7.5KVAR