| NEC Table
110.26 |
| Nominal Voltage
to Ground |
Minimum Clear
Distance |
|
Condition 1 |
Condition 1 |
Condition 1 |
| 0 - 150 |
900mm (3 ft) |
900mm (3 ft) |
900mm (3 ft) |
| 151 - 600 |
900mm (3 ft) |
1.1m
(3-1/2 ft) |
1.2m
(4 ft) |
|
Condition 1 Exposed
live parts on one side of the working space and no live or grounded
parts on the other side of the working space, or exposed live parts on
both sides of the working space that are effectively guarded by
insulating materials. |
|
Condition 2 Exposed live
parts on one side of the working space and grounded parts on the other
side of the working space. Concrete, brick, or tile walls shall be
considered as grounded. |
|
Condition 3 Exposed live
parts on both sides of the working space. |
| Article 430-110 |
| States that the
disconnecting means for motor circuits rated at 600 volts or less shall
have an ampere rating not less than 115 percent of the full-load current
rating of the motor. Unless it is non-fusible rated for the
horsepower being served. |
Click Here
for 3 Phase motor load table
Click Here
for 1 Phase motor load table
Click Here for Maximum Fuse
Motor Protection. |