Table 310.16 Allowable Ampacities of Insulated Conductors Rated 0
Through 2000 Volts, 60°C Through 90°C (140°F Through 194°F), Not
More than Three Current-Carrying Conductors in Raceway, Cable, or
Earth (Directly Buried), Based on Ambient Temperature of 30°C
(86°F) |
|
|
60° C (140° F) |
75° C (167° F) |
90° C (194° F) |
60° C (140° F) |
75° C (167° F) |
90° C (194° F) |
|
|
Size AWG or kcmil |
Types TW, UF |
Types RHW, THHW, THW, THWN, XHHW, USE, ZW |
Types TBS, SA, SIS, FEP, FEPB, MI, RHH, RHW-2, THHN, THHW ,THW-2,
THWN-2, USE-2, XHH, XHHW, XHHW-2, ZW-2 |
TYPES TW, UF |
Types, RHW, THHW, THW, THWN, XHHW, USE |
Types TBS, SA, SIS, THHN, THWN, THW-2, THWN-2,
RHH , RHW2, USE-2, XHH, XHHW, XHHW-2, ZW-2 |
Size AWG or kcmil |
|
|
COPPER |
ALUMINUM OR COPPER-CLAD ALUMINUM |
|
|
18 |
- |
- |
14 |
- |
- |
- |
- |
|
16 |
- |
- |
18 |
- |
- |
- |
- |
|
14* |
20 |
20 |
25 |
- |
- |
- |
- |
|
12* |
25 |
25 |
30 |
20 |
20 |
25 |
12* |
|
10* |
30 |
35 |
40 |
25 |
30 |
35 |
10* |
|
8 |
40 |
50 |
55 |
30 |
40 |
45 |
8 |
|
6 |
55 |
65 |
75 |
40 |
50 |
60 |
6 |
|
4 |
70 |
85 |
95 |
55 |
65 |
75 |
4 |
|
3 |
85 |
100 |
110 |
65 |
75 |
85 |
3 |
|
2 |
95 |
115 |
130 |
75 |
90 |
100 |
2 |
|
1 |
110 |
130 |
150 |
85 |
100 |
115 |
1 |
|
1/0 |
125 |
150 |
170 |
100 |
120 |
135 |
1/0 |
|
2/0 |
145 |
175 |
195 |
115 |
135 |
150 |
2/0 |
|
3/0 |
165 |
200 |
225 |
130 |
155 |
175 |
3/0 |
|
4/0 |
195 |
230 |
260 |
150 |
180 |
205 |
4/0 |
|
250 |
215 |
255 |
290 |
170 |
205 |
230 |
250 |
|
300 |
240 |
285 |
320 |
190 |
230 |
255 |
300 |
|
350 |
260 |
310 |
350 |
210 |
250 |
280 |
350 |
|
400 |
280 |
335 |
380 |
225 |
270 |
305 |
400 |
|
500 |
320 |
380 |
430 |
260 |
310 |
350 |
500 |
|
600 |
355 |
420 |
475 |
285 |
340 |
385 |
600 |
|
700 |
385 |
460 |
520 |
310 |
375 |
420 |
700 |
|
750 |
400 |
475 |
535 |
320 |
385 |
435 |
750 |
|
800 |
410 |
490 |
555 |
330 |
395 |
450 |
800 |
|
900 |
435 |
520 |
585 |
355 |
425 |
480 |
900 |
|
1000 |
455 |
545 |
615 |
375 |
445 |
500 |
1000 |
|
1250 |
495 |
590 |
665 |
405 |
485 |
545 |
1250 |
|
1500 |
520 |
625 |
705 |
435 |
520 |
585 |
1500 |
|
1750 |
545 |
650 |
735 |
455 |
545 |
615 |
1750 |
|
2000 |
560 |
665 |
750 |
470 |
560 |
630 |
2000 |
|
CORRECTION FACTORS |
|
Ambient Temp. (° C) |
For ambient temperatures other than 30°C (86°F), multiply the
allowable ampacities shown above by the appropriate factor shown
below. |
Ambient Temp. (° F) |
|
21 - 25 |
1.08 |
1.05 |
1.04 |
1.08 |
1.05 |
1.04 |
70 -b 77 |
|
26 - 30 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
78 - 86 |
|
31 - 35 |
0.91 |
0.94 |
0.96 |
0.91 |
0.94 |
0.96 |
87 - 95 |
|
36 - 40 |
0.82 |
0.88 |
0.91 |
0.82 |
0.88 |
0.91 |
96 - 104 |
|
41 - 45 |
0.71 |
0.82 |
0.87 |
0.71 |
0.82 |
0.87 |
105 - 113 |
|
46 - 50 |
0.58 |
0.75 |
0.82 |
0.58 |
0.75 |
0.82 |
114- 122 |
|
51 - 55 |
0.41 |
0.67 |
0.76 |
0.41 |
0.67 |
0.76 |
123 - 131 |
|
56 - 60 |
|
0.58 |
0.71 |
|
0.58 |
0.71 |
132 - 140 |
|
61 - 70 |
|
0.33 |
0.58 |
|
0.33 |
0.58 |
141 - 158 |
|
71 - 80 |
|
|
0.41 |
|
|
0.41 |
159 - 176 |
|
*See 240,4(D) |
|
|
|
|
|
|
|