Table B.310.11
Adjustment Factors for More Than Three Current-Carrying Conductors in
a Raceway or Cable with Load Diversity |
Number of
Current- Carrying Conductors |
Percent of
Values in Tables as Adjusted for Ambient Temperature if Necessary
|
4 – 6
|
80
|
7 – 9
|
70
|
10 – 24
|
70*
|
25 – 42
|
60*
|
43 – 85
|
50*
|
*These factors
include the effects of a load diversity of 50 percent. |
FPN: The
ampacity limit for the number of current-carrying conductors in 10
through 85 is based on the following formula. For greater than 85
conductors, special calculations are required that are beyond the
scope of this table. |

|
where:
A1= ampacity from Table 310.16; Table 310.18; Table B.310.1; Table
B.310.6; and Table B.310.7 multiplied by the appropriate factor from
Table B.310.11.
N= total number of conductors used to obtain multiplying factor from
Table B.310.11
E= desired number of current-carrying conductors in the raceway or
cable
A2= ampacity limit for the current-carrying conductors in the raceway
or cable |
|