Notice: NEC is a registered trademark of the National Fire Protection Association, Inc.  All NEC references by Electrical Helper are interpretations of the NEC by the Electrical Helper staff and are not NEC statements. The official position of the NEC requires that the NEC be referred to in its entirety. 
Table B.310.11 Adjustment Factors for More Than Three Current-Carrying Conductors in a Raceway or Cable with Load Diversity
Number of Current- Carrying Conductors Percent of Values in Tables as Adjusted for Ambient Temperature if Necessary
4 – 6 80
7 – 9 70
10 – 24 70*
25 – 42 60*
43 – 85 50*
*These factors include the effects of a load diversity of 50 percent.
FPN: The ampacity limit for the number of current-carrying conductors in 10 through 85 is based on the following formula. For greater than 85 conductors, special calculations are required that are beyond the scope of this table.

where:
A1= ampacity from Table 310.16; Table 310.18; Table B.310.1; Table B.310.6; and Table B.310.7 multiplied by the appropriate factor from Table B.310.11.
N= total number of conductors used to obtain multiplying factor from Table B.310.11
E= desired number of current-carrying conductors in the raceway or cable
A2= ampacity limit for the current-carrying conductors in the raceway or cable