Table 400.5(A) Allowable
Ampacity for Flexible Cords and Cables |
|
[Based on
Ambient Temperature of 30°C (86°F). See 400.13 and Table 400.4.] |
| |
|
Thermoset Types C, E, EO, PD, S, SJ, SJO,
SJOW, SJOO, SJOOW, SO, SOW, SOO, SOOW, SP-1, SP-2, SP-3, SRD, SV,
SVO, SVOO |
|
|
Size (AWG) |
Thermoplastic Types TPT, TST |
Thermoplastic Types ET, ETLB, ETP, ETT,
SE, SEW, SEO, SEOW, SEOOW, SJE, SJEW, SJEO, SJEOW, SJEOOW, SJT, SJTW,
SJTO, SJTOW, SJTOO, SJTOOW, SPE-1, SPE-2, SPE-3, SPT-1, SPT-1W,
SPT-2, SPT-2W, SPT-3, ST, SRDE, SRDT, STO, STOW, STOO, STOOW, SVE,
SVEO, SVT, SVTO, SVTOO |
Types HPD, HPN, HSJ, HSJO, HSJOO |
| |
|
Column A+ |
Column B+ |
|
|
27* |
0.5 |
— |
— |
— |
|
20 |
— |
5** |
*** |
— |
|
18 |
— |
7 |
10 |
10 |
|
17 |
— |
9 |
12 |
13 |
|
16 |
— |
10 |
13 |
15 |
|
15 |
— |
12 |
16 |
17 |
|
14 |
— |
15 |
18 |
20 |
|
12 |
— |
20 |
25 |
30 |
|
10 |
— |
25 |
30 |
35 |
|
8 |
— |
35 |
40 |
— |
|
6 |
— |
45 |
55 |
— |
|
4 |
— |
60 |
70 |
— |
|
2 |
— |
80 |
95 |
— |
*Tinsel cord.
**Elevator cables only.
***7 amperes for elevator cables only; 2 amperes for other types.
+The allowable currents under
Column A apply to
3-conductor cords and other multiconductor cords connected to
utilization equipment so that only 3 conductors are
current-carrying. The allowable currents under
Column B apply to
2-conductor cords and other multiconductor cords connected to
utilization equipment so that only 2 conductors are
current-carrying.
|
| |
|