Table 250.122 Minimum Size Equipment Grounding Conductor
for Grounding Raceway and Equipment |
|
Rating or Setting of automatic Overcurrent Device in
Circuit Ahead of Equipment, Conduit, etc., Not Exceeding
(Amperes) |
|
|
|
Size (AWG or kcmil) |
|
Copper |
Aluminum or Copper-Clad Aluminum* |
|
15 |
14 |
12 |
|
20 |
12 |
10 |
|
30 |
10 |
8 |
|
40 |
10 |
8 |
|
60 |
10 |
8 |
|
100 |
8 |
6 |
|
200 |
6 |
4 |
|
300 |
4 |
2 |
|
400 |
3 |
1 |
|
500 |
2 |
1/0 |
|
600 |
1 |
2/0 |
|
800 |
1/0 |
3/0 |
|
1000 |
2/0 |
4/0 |
|
1200 |
3/0 |
250 |
|
1600 |
4/0 |
350 |
|
2000 |
250 |
400 |
|
2500 |
350 |
600 |
|
3000 |
400 |
600 |
|
4000 |
500 |
800 |
|
5000 |
700 |
1200 |
|
6000 |
800 |
1200 |
|
Note: Where necessary to comply with 250.4(A)(5) or
(B)(4), the equipment grounding conductor shall be sized
larger than given in the table |
|
*See installation restrictions in 250.120 |
|
|
|