| NEC is a registered trademark of the National Fire Protection Association, Inc. All NEC references by Electrical Helper are interpretations of the NEC by the Electrical Helper staff and are not NEC statements. The official position of the NEC requires that the NEC be referred to in its entirety. | ||
|
|
Article 400-9 Splices Flexible cord shall be used only in continuous lengths without splice or tap where initially installed in applications permitted by 400.7(A). The repair of hard-service cord and junior hard-service cord (see Trade Name column in Table 400.4) 14 AWG and larger shall be permitted if conductors are spliced in accordance with 110.14(B) and the completed splice retains the insulation, outer sheath properties, and usage characteristics of the cord being spliced. |
|
|
|
400.12 Minimum Size. The individual conductors of a flexible cord or cable shall not be smaller than the sizes in Table 400.4. |
|
|
|
400.23 Equipment Grounding
Conductor Identification. A conductor intended to be used as an equipment grounding conductor shall have a continuous identifying marker readily distinguishing it from the other conductor or conductors. Conductors having a continuous green color or a continuous green color with one or more yellow stripes shall not be used for other than equipment grounding conductors. The identifying marker shall consist of one of the methods in 400.23(A) or (B). |